ESHER, SURREY

1/6

Diagnosis

We found evidence of severe condensation above the indoor pool on the underside of the external podium deck. The deck was insulated from below but with no continuous vapour barrier. The condensation had aged the insulation, rusted the fixing rails and water then ponded on the stretch ceiling below.

 

Solution

We replaced the insulation with directly bonded 120mm Foamglas resulting in adequate insulation and a continuous vapour barrier with one product.